SPC Troubleshooting ​

Last updated

SymptomCauseFix
"No data points yet. Waiting for trigger events..."Trigger tag has not changed; tags not subscribed; device offlineCheck the trigger tag changes on the device page. Both tags must be subscribed on the group's device.
Tag dropdowns are emptyNo subscribed tags on the group's deviceSubscribe the tags first.
Two samples per partTrigger changes to two different non-zero values per part (e.g. 1 then 2 before resetting)Pulse a single value, or trigger on a counter.
No samples from a "part done" bitThe bit stays at 1 between parts, so the value doesn't changeHave the PLC drop the bit back to 0 after each part.
Samples stop while another part runsGroup has a Program name that differs from the device's program tagExpected. Create a group per program.
Samples are one part behindMeasurement and trigger update in the same pollUpdate the measurement before the trigger in the PLC.
Some samples missingMeasurement value was non-numeric at trigger timeCheck the tag's data type and quality.
Older samples no longer on the plotThe plot shows the latest 200 samplesRead older samples with GET /api/spc/charts/:chartId/data?to=….
UCL/LCL never appearFewer than 25 samples, or all samples identical (σ = 0)Wait for the baseline to fill, or enter the limits.
UCL/LCL do not follow the latest dataBy design: limits are frozen once establishedExpected. After a real process change, use Recalculate the control limits.
Limits look wrong after a machine rebuildThey still describe the process before the changeRecalculate them, or enter limits from a fresh capability study.
A limit says "set by an earlier version"An earlier release saved automatic limits where typed-in ones go, so they cannot be told apartRecalculate, or clear with PUT /api/spc/charts/:id {"ucl": null, "lcl": null} to re-baseline.
"Need 25 samples to recalculate control limits"The chart has fewer samples than the recalculation windowWait for more samples.
Cp shows "—"Only one spec limit, fewer than 2 samples, or σ = 0Set both USL and LSL.
Cpk shows "—"No spec limitsSet USL and/or LSL.
No shield icon, Mean line or Cpk trendEnhanced SPC is offAdmin: System > Settings → Feature Toggles.
403 Insufficient permissions adding a manual valueManual entry needs editorUse an editor account.
403 deleting a groupDeleting groups needs adminAsk an admin.
"chartName, readVariable, and triggerVariable are required"API call missing fieldsSupply all three.
"SPC chart not found" / "SPC group not found"Wrong id or already deletedList groups and charts to get ids.