License feature: Ladder LogicEvery operand — a contact's Tag, a compare's Source A, a math block's Destination — has a source type chosen from a drop-down.
| Type | What it is | Read | Write |
|---|---|---|---|
| Device Tag | A tag on any device, including Local Tags. Click Browse to pick it; the box then shows Device #3 / Line1/Speed | The value at the start of the scan | Collected and written after the scan (see below) |
| Task Tag | Internal memory shared by every program in this task | Immediately | Immediately |
| Program Tag | Internal memory private to this program | Immediately | Immediately |
| Literal | A constant typed in the box (Constant value), e.g. 450, 2.5, 1 | Always that value | Cannot be written |
A new contact or coil starts as Device Tag with Not set. An operand left unset reads as 0 / false and writes nowhere.
Task Tag and Program Tag addresses
Type an address in the box (e.g. B3:0/0, N7:0, F8:0). The first letter(s) decide the type; the rest is just a name, so you can use Allen-Bradley style addresses or readable names:
| Starts with | Type | Examples | Stored as |
|---|---|---|---|
B | Bit | B3:0/0, B_Motor_Run | on/off; writing 1 or true sets it |
N | Integer | N7:0, N_PartCount | whole number — writes are rounded |
F | Float | F8:0, F_TempC | decimal number |
ST | String | ST9:0, ST_Recipe | text (only DTOS writes text) |
Tn:n | Timer | T4:0, T4:0/DN, T4:0.ACC | a timer given that address (see below) |
Cn:n | Counter | C5:0, C5:0/DN, C5:0.ACC | a counter given that address |
| anything else | — | Count, Temp | not stored — reads give 0 |
Warning: Apart from timer and counter addresses, only the first letter counts: a name like
Flowis a float,Batchis a bit, andCountis ignored.
Timer and counter addresses
Give a TON, TOF, RTO, CTU or CTD an Address (a Task or Program Tag such as T4:0 or C5:0) and other elements can use its members:
| Member | Timer | Counter | Writable |
|---|---|---|---|
/DN (or the bare address) | done | done | no |
/TT | timing | — | no |
/EN | rung power into the timer | — | no |
/CU, /CD | — | rung power into the counter | no |
.ACC | accumulated milliseconds | count | yes |
.PRE | preset (ms) | preset | yes — replaces the element's Preset; the written value is kept across Save, Stop/Run and restarts until written again |
- RES clears the addressed timer or counter.
- Elements with the same address share one timer or counter, as on a PLC.
- A Task Tag address is shared by all programs in the task; a Program Tag address is private to the program.
Internal tags are not visible outside the task: you can't show them on a dashboard or use them in a workflow. They start at 0 (or empty), and are saved every 10 s and when the task stops. Copy a value to a Local Tags tag when something else needs it.
How values are read
- Contacts (XIC, XIO, OSR, OSF) treat
trueand1as on,falseand0as off, any other number as on if it is not 0, and any other text as off. - Numeric operands convert the value to a number; text that isn't a number becomes 0.
- Coils write
1and0, nottrue/false.
Where device-tag writes go
| Device | What happens |
|---|---|
| Local Tags | The tag is updated when the value changes; dashboards, workflows, scripts and alarms see it |
| Simulator | The simulated value is updated when it changes |
| A real device (PLC, robot, drive…) | The driver writes the device when the value changes. If the device still reads a different value two seconds later — another HMI changed it, or a write was lost — it is written again. It is never written every scan |
- The device needs Tag Write Access turned on (device settings). If it is off, nothing is sent and the task log gets a write_error entry naming the tag and device, at most once a minute per output.
- A failed write (device offline, driver refused it) is logged the same way; the next change is sent as usual.
- Writes are not permission-checked per user: the task acts as the system.
Examples
| Element | Setting |
|---|---|
| XIC | Tag: Device Tag Conveyor PLC Conveyor_Running — passes power while the conveyor runs |
| GRT | Source A: Device Tag Furnace/Temp; Source B: Literal 450 |
| MOV | Source: Literal 0; Destination: Program Tag N_RecipeStep |
| OTE | Tag: Device Tag Local Tags Line1/Ready — for the HMI |