Cookbook: Conveyor Start Interlock in Ladder Logic ​

Last updated

License feature: Ladder Logic

Line 2's infeed conveyor may only start when the E-stop circuit is healthy, the guard is closed, air pressure is at least 85 psi, the downstream machine isn't blocked and the PLC is communicating. Operators request start and stop from a dashboard. This recipe computes the permissive in Scada.Ink ladder logic and passes a run permit and a heartbeat to the PLC.

Warning: This is an operational permissive, not a safety function. E-stops and guards must be wired through safety-rated hardware in the machine. Scada.Ink logic runs on a general-purpose appliance, shares a thread with the web server, and a stopped task leaves its outputs as they were.

What shapes the design ​

Ladder can't write to a PLC tag the appliance is already reading. For such a tag, a ladder output only changes the value Scada.Ink shows until the next poll replaces it; the PLC isn't written. See Tags and Addresses. So the logic writes Local Tags, and a workflow copies them to the PLC once a second — the documented workaround.

Start/stop uses latch and unlatch rungs. A classic seal-in rung (Start in parallel with a Run contact) can also be drawn with a parallel branch (see The Ladder Editor); this recipe keeps the latch form because each rung then reads on its own in Monitor mode. See Common Ladder Patterns.

The signals ​

Line 2 PLC — Modbus TCP at 10.20.2.40, register map (zero-based holding registers):

Tag path (register name)AddressDirectionMeaning
L2/EStopOK0read1 = E-stop circuit healthy
L2/GuardClosed1read1 = infeed guard closed
L2/AirPressure_x102readpsi × 10 (850 = 85.0 psi)
L2/DownstreamBlocked3read1 = downstream machine full or faulted
L2/ConveyorPermit10write1 = Scada.Ink permits running
L2/Heartbeat11writeCounts up once a second while the logic runs

Local Tags (create on the Local Tags page, all int, default 0, Persist unticked):

Tag PathWritten byPurpose
Line2/StartReqDashboard buttonOperator start request; ladder clears it
Line2/StopReqDashboard buttonOperator stop request; ladder clears it
Line2/ConveyorPermitLadderThe permit, copied to the PLC
Line2/HeartbeatLadderThe heartbeat, copied to the PLC
Line2/BootedLadder0 after every restart; lets the logic drop the permit at start-up

Step 1: Add the PLC ​

  1. Devices → Add Device → Modbus TCP: Device Name Line 2 PLC, IP Address 10.20.2.40, Port 502, Polling Rate (ms) 250, tick Allow Tag Writes → Create Device.
  2. Set the register map through the API (Advanced Driver Settings):
json
{
  "driverConfig": {
    "registers": [
      { "name": "L2/EStopOK", "address": 0, "type": "hr", "data_type": "int" },
      { "name": "L2/GuardClosed", "address": 1, "type": "hr", "data_type": "int" },
      { "name": "L2/AirPressure_x10", "address": 2, "type": "hr", "data_type": "int" },
      { "name": "L2/DownstreamBlocked", "address": 3, "type": "hr", "data_type": "int" },
      { "name": "L2/ConveyorPermit", "address": 10, "type": "hr", "data_type": "int" },
      { "name": "L2/Heartbeat", "address": 11, "type": "hr", "data_type": "int" }
    ]
  }
}
  1. Disconnect / Connect, then Browse Tags → tick all six → Subscribe Selected. The two output registers are subscribed only so the workflow's tag picker can offer them and you can see what the PLC holds; the ladder must never use them.

Step 2: Create the task ​

  1. Ladder Logic → New Task: Task Name Line 2 Interlocks, Scan Mode Periodic, Period (ms) 100 → Create.
  2. In Routines, Add Program → Conveyor. It gets a Main routine.
  3. Gear (Task Settings) → tick Enabled → Save, so the task starts again after a restart.

Step 3: Enter the rungs ​

For each rung: Add Rung, click the rung, click instructions in the palette (each is added at the right-hand end), then click each element and set its operands. B_… and N_… are Program Tag addresses (type them in the box). Paths with a slash are Device Tag operands picked with Browse: Line2/… on Local Tags, L2/… and _STATUS/Connected on Line 2 PLC.

RungElements, left to rightPurpose
1XIO Line2/Booted → OTU B_Run → OTU Line2/ConveyorPermit → OTL Line2/BootedFirst scan after a restart: drop the run bit and the permit
2XIC _STATUS/Connected → XIC L2/EStopOK → XIC L2/GuardClosed → GEQ Source A L2/AirPressure_x10, Source B Literal 850 → XIO L2/DownstreamBlocked → OTE B_PermissiveThe permissive: all conditions in series
3XIC Line2/StartReq → XIC B_Permissive → OTL B_RunStart only if permitted
4XIC Line2/StartReq → OTU Line2/StartReqClear the start request
5XIC Line2/StopReq → OTU B_RunStop
6XIC Line2/StopReq → OTU Line2/StopReqClear the stop request
7XIO B_Permissive → OTU B_RunAny interlock lost drops the run bit
8OSR B_Run → OTL Line2/ConveyorPermitPublish the permit on the rising edge only
9OSF B_Run → OTU Line2/ConveyorPermit…and on the falling edge
10XIO B_Pulse → TON Preset (ms) 1000 → OTE B_PulseOne-second pulse
11XIC B_Pulse → ADD Source A N_Heartbeat, Source B Literal 1, Destination N_Heartbeat → MOV Source N_Heartbeat, Destination Line2/HeartbeatHeartbeat once a second
12GEQ N_Heartbeat ≥ Literal 30000 → CLR N_HeartbeatKeep it inside a 16-bit register

Click Save, then Run.

Why it's built this way:

  • Rung order is the priority. Stop (rung 5) and the interlock (rung 7) come after start (rung 3), so if start and stop arrive in the same scan, stop wins.
  • Requests are cleared by the logic. Device-tag and Local Tags values are read at the start of the scan and written at the end, so rung 3 still sees the request that rung 4 clears.
  • Program tags change immediately, so the OSR/OSF in rungs 8–9 see B_Run change in the same scan. Publishing only on edges keeps Local Tags writes rare; an OTE on a local tag would write it ten times a second.
  • Restart behavior. B_Run is restored from saved state after a restart, so on its own the permit could come straight back. Line2/Booted is not persistent, so it is 0 after every restart and rung 1 drops the run bit: the conveyor needs a fresh start request.
  • _STATUS/Connected drops the permissive if the PLC stops communicating. Otherwise the logic would keep using the last values it received, because ladder ignores tag quality.

Step 4: Copy the permit and heartbeat to the PLC ​

  1. Workflows → New Workflow → Line 2 permit to PLC → Create.
  2. Add and wire, in order:
NodeSettings
ScheduleType Interval, Interval (ms) 1000
Set TagTag Path Line 2 PLC → L2/ConveyorPermit; Value Source From another tag; Source Device Local Tags; Source Tag Line2/ConveyorPermit
Set TagTag Path Line 2 PLC → L2/Heartbeat; Value Source From another tag; Source Device Local Tags; Source Tag Line2/Heartbeat
  1. Save, then set it to Enabled.

Don't use a Tag Change trigger on the local tags here. A schedule rewrites the PLC every second whatever happened, so a PLC that restarts gets the current permit within a second.

Note: Set Tag does not report a write the device refuses — the run still shows as completed. That's why the PLC checks the heartbeat rather than trusting that the permit was delivered.

Step 5: PLC side ​

In the PLC program:

  1. Run the conveyor only while ConveyorPermit (register 10) = 1 and the heartbeat (register 11) has changed within the last 3 seconds.
  2. If the heartbeat stops changing, drop the run output. This covers a stopped ladder task, a stopped workflow, a crashed appliance and a network break — Stop in Scada.Ink leaves Line2/ConveyorPermit at its last value, so the heartbeat is what makes the PLC safe to rely on.
  3. Keep the hardwired E-stop and guard circuits in the safety relay regardless.

Step 6: Operator buttons and status ​

On the Line 2 dashboard:

WidgetSettings
Button "Start conveyor"Action Write Tag, Write Tag Line2/StartReq, Write Value 1, Color green
Button "Stop conveyor"Action Write Tag, Write Tag Line2/StopReq, Write Value 1, Color red
Status "Permit"value → Line2/ConveyorPermit; rules = equals 1 → PERMITTED green, = equals 0 → NOT PERMITTED gray
Value "Heartbeat"value → Line2/Heartbeat
Status "Guard"value → L2/GuardClosed; equals 1 → Closed green, equals 0 → OPEN red
Value "Air"value → L2/AirPressure_x10; Multiply by 0.1, Unit psi, Decimals 1

Operators can press Write Tag buttons (operator role is enough). They could also press a button that starts or stops the ladder task itself; to prevent that, switch the task to Restricted and grant run only to the people who should.

Step 7: Test before connecting the conveyor ​

There's no force function. With the PLC's run output disabled:

  1. Open the editor in Monitor mode. Rung 2 is green up to the first false condition.
  2. Open the guard: rung 2's XIC L2/GuardClosed goes gray, B_Permissive drops, rung 7 unlatches B_Run, and within a second the PLC's register 10 reads 0.
  3. Close the guard and press Start conveyor: Line2/StartReq goes 1 then back to 0, the permit goes to 1.
  4. Press Stop conveyor and check the permit drops.
  5. Stop the task with Stop: the permit stays 1 in Scada.Ink, the heartbeat stops, and the PLC must drop the run output within 3 seconds.
  6. Restart the Scada.Ink service: after it comes back, the permit is 0 until someone presses Start.

To test a condition you can't create physically, temporarily bind that contact to a Local Tags test tag and toggle it from a dashboard, then bind it back and Save.

Timing ​

PathWorst case
Guard opens → PLC register updatedModbus poll (250 ms) + ladder scan (100 ms) + workflow interval (1 s) ≈ 1.4 s
Scada.Ink stops → PLC drops runHeartbeat timeout in the PLC (3 s)

Anything that must react faster than that belongs in the PLC.

Troubleshooting ​

SymptomCauseFix
Coil looks on in Monitor but the PLC register doesn't changeThe ladder wrote a PLC tag directlyWrite Line2/… on Local Tags; let the workflow copy it
Permit never goes to 1A permissive input false, or _STATUS/Connected falseFollow rung 2 in Monitor to the first gray element
Start request stays at 1Task not running, or rung 4 bound to a different tagCheck the task status and the operand
PLC register 10 doesn't follow the local tagWorkflow disabled, Allow Tag Writes off (Write access not enabled for device … in History), or wrong source tagCheck the workflow's History and the device settings
Task stopped after a restartEnabled not ticked in Task SettingsTick it and Save
Heartbeat stuckTask stopped or faultedCheck the status bar for a fault
Dashboard Start button: "Local tag not found"Line2/StartReq not createdCreate it on the Local Tags page