OPC-UA Server
Last updated
The appliance has a built-in OPC-UA server that lets other systems — a plant SCADA, an MES, a historian, UaExpert — browse and read the tags you choose, and optionally write to them. It is off by default, and nothing is exposed until you pick tags.
This article covers the server. Choosing which tags to expose is also covered in Writing Tag Values & OPC-UA Exposure. To read from another OPC-UA server, add an OPC-UA device instead — see Open Standards.
Where and who
System → Settings, card OPC-UA Server. Needs admin. The server is part of every edition — there is no separate license feature. Its state also appears on Driver Health.
Turn the server on
- Open System → Settings and find OPC-UA Server.
- Tick Enable server.
- Leave Port at 4840 unless something else uses it.
- Leave Security Policy at
Basic256Sha256and Security Mode atSignAndEncryptunless a client cannot support them. - Set Username and Password for clients, or tick Allow anonymous access on an isolated network.
- Click Save & apply. The badge next to the title changes to Running.
- Expose tags (next procedure). Until you do, the address space is empty.
Settings
| Field | What it does | Default | Allowed values |
|---|---|---|---|
| Enable server | Start the server now and at every API start | off | on / off |
| Port | TCP port clients connect to | 4840 | 1–65535; Port must be between 1 and 65535 otherwise |
| Allow anonymous access | Accept clients without a user name. Also adds security policy None and mode None to the endpoints | off | on / off |
| Security Policy | Encryption algorithm set offered to clients | Basic256Sha256 | Basic256Sha256, Aes128_Sha256_RsaOaep, Aes256_Sha256_RsaPss, None |
| Security Mode | Message protection | SignAndEncrypt | SignAndEncrypt, Sign, None |
| Username | The one user name clients may sign in with | opcua | any text |
| Password | That user's password; stored encrypted. Shows (set — leave blank to keep) once set | none | cannot be cleared from the form once set |
- One account. The server does not use Scada.Ink user accounts or roles. Every client that signs in uses the single Username/Password pair, and every signed-in (or anonymous) session has the same rights.
- With anonymous off and no password, the form warns Set a password — with anonymous off and no password, no client can connect.
- Choose policy and mode as a pair:
NonewithNone, or a secure policy withSignorSignAndEncrypt. The form does not stop you choosingNonewithSignAndEncrypt, which clients cannot use.
Endpoint
text
opc.tcp://<appliance-address>:4840/scadaink/serverThe server advertises the appliance's host name and every IPv4 address it has. If clients reach it through a different name (NAT, DNS alias), set the environment variable OPCUA_ALTERNATE_HOSTNAMES (comma-separated) for the API service.
Certificates
- The server creates its own self-signed application certificate on first start and keeps it in the
opcua-pkifolder next to the database (orOPCUA_PKI_DIR). It survives restarts, so clients only need to trust it once. - New client certificates are refused by default. A client connecting to a secure endpoint (Sign or Sign & Encrypt) for the first time is refused and its certificate listed under Pending on the OPC-UA Server card — trust it there to let that client connect, no restart needed. Turn on Accept new client certificates automatically (off by default) while commissioning to trust every new client on first connect, then turn it back off. Anonymous connections with security None don't use a client certificate and are unaffected.
- Trusted clients are still accepted even if their certificate has expired or its start date hasn't arrived yet — PLC and HMI clocks are often wrong and their certificates rarely get renewed. The card marks an out-of-date trusted certificate as expired — still accepted rather than an error.
- In the client, trust the server certificate when prompted (UaExpert: Accept the server certificate permanently).
Expose tags
| Kind of tag | Where | Controls |
|---|---|---|
| Device tags | Devices → device → Manage Tags tab, edit a row | Expose, server name, Writable |
| Local tags | Local Tags, the OPC-UA pill on a row | Expose on OPC-UA, Server name, Writable, Save |
| Expression tags | Expression Tags, the OPC-UA icon on a row | Expose on OPC-UA (read-only), Server name, Save |
| UDT instances | Tag UDTs, the OPC-UA pill on an instance | Exposes (and optionally makes writable) every member tag |
Rows show OPC R or OPC R/W once exposed. Only enabled tags appear.
Address space
text
Objects
├── Devices
│ ├── Press 4 (#3) ns=1;s=device:3
│ │ └── Press_4_HR100 ns=1;s=dev3:Press_4_HR100
│ └── Local Tags (#1)
│ └── Local_BatchCount ns=1;s=dev1:Local_BatchCount
└── Expression Tags ns=1;s=expressions
└── OEE_Line3 ns=1;s=expr:12- Browse name is the Server name you typed, or by default the device name and tag path joined with
_(/,:,.and spaces become_). Give each exposed tag a unique name within its device. When two tags share one, the tag already on the server keeps it and the other is served with a number added (Speed_2); the OPC-UA Server card lists each such tag by name until you rename one. - NodeIds are strings built from the device id and browse name, so renaming a tag's server name changes its NodeId and breaks clients that stored it. The namespace index is normally 1; browse rather than hard-code it.
- Data types: float/real/double → Double; int/integer → Int32; bool → Boolean; anything else → String.
- Values come from the appliance's live cache when a client reads; the minimum sampling interval is 500 ms.
- Quality is not passed on. Every value reads with status Good and no source timestamp. A tag whose device is offline reads 0, false or an empty string. If a client must detect stale data, also expose the device's
_STATUS/Connectedtag.
Writes
A client can write to a node only when all of these are true:
- The tag is exposed with Writable ticked (expression tags are never writable).
- The device has Allow Tag Writes turned on. Otherwise the write is refused with
BadUserAccessDenied.
Note: Local tags are the exception. A tag on the built-in Local Tags device only needs to be exposed as writable; that device's Allow Tag Writes switch is not checked, the same as for writes from the Local Tags page and the REST API.
Things to know:
- No per-user control. Security levels and roles do not apply to OPC-UA; any session that can connect can write every writable node.
- Device writes are confirmed. For a PLC or other driver device, the server waits for the device's answer before replying.
Goodmeans the device took the value. If the device refuses the write or can't be reached, the client getsBadDeviceFailure, orBadCommunicationErrorwhen the driver service itself is down, and the API log showsOPC-UA write to … did NOT apply: …with the reason. When the device is slow or unreachable the reply can take several seconds, so give the client a request timeout of at least 10 seconds. - Every write that is applied is recorded in the Audit Log as
opcua_writewith the value, tag and device. Refused and failed writes are not.
Restarts and live changes
- Save & apply restarts the server when a server setting changed (port, security, user name, password, certificate acceptance). Connected clients are disconnected and must reconnect.
- Tag changes don't restart it. Exposing a tag, changing its server name or Writable flag (on any page) adds, replaces or removes just that node about half a second later; connected clients stay connected. A client monitoring a node that was removed gets a bad status for it.
- Deleting a tag or device, disabling a tag, or renaming a device is picked up within 15 seconds: the node is removed, or the device folder is renamed.
- When the API starts, the server starts automatically if Enable server is on.
Status
- The Running / Stopped badge on the settings card.
- Driver Health shows OPC-UA server running — Exposing tags on port 4840, or OPC-UA server enabled but not running when it failed to start.
- If the server can't start, Save & apply shows the error, and while it stays stopped the card shows the reason under the settings (for example
listen EADDRINUSE: address already in use :::4840).
| Method | Path | Role | Purpose |
|---|---|---|---|
| GET | /api/opcua/settings | admin | Settings plus hasPassword, running, lastError and nameConflicts |
| PUT | /api/opcua/settings | admin | Save and apply; answers { running }, or 500 with the reason when the server can't start |
| GET | /api/driver-health | viewer | Includes opcuaServer: { enabled, running, port, lastError, nameConflicts } |
Troubleshooting
| Symptom | Cause | Fix |
|---|---|---|
| Badge shows Stopped after Save & apply | Port already in use, or another start error — the card shows which | Try a different port, then Save & apply again; contact Scada.Ink support if it still won't start |
| Card lists tags that share a browse name | Two exposed tags on one device have the same server name | Give one of them its own Server name |
Client: BadUserAccessDenied / BadIdentityTokenRejected on connect | Wrong user name or password, or anonymous off | Use the Username/Password from the card |
| Client cannot find an endpoint matching its security | Client wants None but anonymous is off, or a policy it does not support | Match the client to the policy/mode shown, or change them |
| Client connects, Devices folder empty | No tags exposed, or the exposed tags are disabled | Expose tags from Manage Tags / Local Tags |
Write returns BadUserAccessDenied | Allow Tag Writes is off on the device (not checked for Local Tags) | Turn it on in the device's Settings tab |
Write returns BadNotWritable | Tag exposed read-only | Tick Writable |
Write returns BadDeviceFailure | The device refused the write or didn't answer (offline, wrong address, or the PLC rejected the value) | Check the API log for did NOT apply and the reason; confirm the device is Connected |
Write returns BadCommunicationError | The driver service isn't running | Check Driver Health and the driver service log |
| Clients disconnect now and then | Someone saved changed server settings, which restarts the server | Configure clients to reconnect |
| Endpoint URL uses a host name clients cannot resolve | Server advertises the appliance host name | Connect by IP, or set OPCUA_ALTERNATE_HOSTNAMES |