The Siemens S7 driver uses ISO-on-TCP (RFC 1006) on port 102. It addresses memory by data block and byte offset, not by symbol name.
One-time PLC setup
S7-1200 / S7-1500 (TIA Portal)
- PLC Properties → Protection & Security → Connection mechanisms: tick Permit access with PUT/GET communication from remote partner.
- For every data block you'll read: DB Properties → Attributes: untick Optimized block access, compile, and note the Offset column that appears.
- Download to the PLC.
S7-300 / S7-400: PUT/GET is allowed by default. Note the CPU's rack and slot in the hardware configuration (usually rack 0, slot 2).
Connection fields
| Field | Value |
|---|---|
| IP Address | CPU's PROFINET/Ethernet port or CP module. |
| Port | 102, the ISO-on-TCP port. Change it only for a router or gateway that forwards another port to the CPU's 102. |
| Rack, Slot | Under Driver Settings. Defaults rack 0, slot 1. |
Slot 1 suits S7-1200/1500 (slot 0 also works on most). S7-300/400 CPUs are normally in slot 2: set Slot to 2 and save.
Address syntax
AREA/TYPE/OFFSET, case-insensitive:
| Example | Reads | Type |
|---|---|---|
DB1/REAL/0 | 4-byte REAL at DB1.DBD0 | float |
DB1/LREAL/0 | 8-byte LREAL | float |
DB1/INT/4 | 2-byte signed INT at DB1.DBW4 | int |
DB1/WORD/6, DB1/UINT/6 | 2-byte unsigned WORD / UINT | int |
DB1/DINT/8 | 4-byte signed DINT at DB1.DBD8 | int |
DB1/DWORD/8, DB1/UDINT/8 | 4-byte unsigned DWORD / UDINT | int |
DB1/TIME/8 | 4-byte TIME, in milliseconds | int |
DB1/BYTE/2, DB1/USINT/2, DB1/SINT/2 | one byte (SINT is signed) | int |
DB1/LINT/0, DB1/ULINT/0, DB1/LWORD/0 | 8-byte integers | int |
DB1/BOOL/12.3 | bit 3 of byte 12 (DB1.DBX12.3) | bool |
DB1/STRING/20 | S7 STRING starting at byte 20 | string |
M/BYTE/10 | merker byte MB10 | int |
M/BOOL/10.2 | merker bit M10.2 | bool |
I/BYTE/0, I/BOOL/0.3 | input byte IB0, input bit I0.3 | int, bool |
Q/WORD/0 | output word QW0 | int |
T/TIMER/5 (or T/5) | timer T5's current value, in milliseconds | int |
C/COUNTER/5 (or C/5) | counter C5's current value, 0–999 | int |
- M, I and Q take every type a DB does.
TandCare the timer and counter areas of S7-300/400 CPUs. S7-1200/1500 timers and counters (TON, CTU…) keep their values in instance data blocks: read theETmember asTIMEandCVasINTfrom that DB (with optimized access off).- The driver speaks the classic S7 protocol, which only knows absolute addresses. To pick tags by name, import the symbols from TIA Portal (below). Optimized blocks have no absolute addresses at all; read those with the Siemens S7 (OPC UA) device type.
- Not supported: DATE_AND_TIME, DTL, WSTRING, arrays and structures as one tag (read their members one by one).
Browse Tags doesn't read the PLC. It lists nine example addresses (DB1/REAL/0, DB1/BOOL/10.0, M/BYTE/0 …), or the symbols you imported and any list in driverConfig.tags. Subscribe real addresses with Manage Tags → Add Tag.
Symbols from TIA Portal (optional)
On the device page, Settings → Driver Settings → TIA Portal symbols → Import from TIA Portal… reads TIA Portal exports in the browser and maps each symbol to its address. Select one or more files:
| Export | How to make it in TIA Portal | Gives |
|---|---|---|
PLC tag table, .xlsx | Open the tag table, Export | I, Q, M, T and C tags with their addresses |
| PLC tag table, CSV or text | Save that .xlsx as CSV, or copy the table's rows (with the header row) into a text file | the same |
Data block source, .db / .scl (plus .udt) | Select the data blocks (and the PLC data types they use), Generate source from blocks | global DBs; the DB number is asked for, since sources do not hold it |
| Openness XML | An Openness export of global DBs, PLC data types or tag tables | the same, with DB numbers |
The import shows how many symbols it found and what it left out, then Add symbols puts them in the table; Save keeps them. Importing again replaces symbols of the same name and keeps the rest. Up to 5,000 symbols per device; arrays are expanded to their first 1,000 elements.
- Browse Tags then lists the symbols by name, such as
"Motor_DB".Speedor"Start_PB", and a tag made from one reads the address behind it. The tag path is the symbol, so after a change to the block, import again and the tag follows the new offset. Quotes are optional:Motor_DB.Speedis the same symbol. - Only standard blocks are imported. A block with Optimized block access on, an instance DB, and members of types the driver can't read (DTL, DATE_AND_TIME, WSTRING, CHAR…) are listed and skipped; the members that follow keep their right offsets. A member whose PLC data type is missing from the files stops that block there: add the data type's source and import again.
- Offsets of data block members are calculated from the declarations with Siemens' standard-access layout rules, since neither export holds them. Compare a few with the Offset column in TIA Portal before relying on them, especially after strings and arrays.
- Peripheral addresses (
%IW64:P) and tags whose data type does not fit their address are skipped.
Writes
With Allow Tag Writes on, every type above can be written in the DB, M and Q areas, plus timers and counters. BOOL is a read-modify-write of its byte; STRING keeps the declared length and refuses longer text; a timer value is converted to S5TIME (up to 9990 s, rounded to the timer's resolution); a counter takes 0–999. A value outside the type's range (for example 70000 into a WORD, or −1 into a UINT) is refused and nothing is written. Inputs (I) aren't writable — the CPU overwrites them every scan.
Worked example: line speed and fault bit from DB10
The PLC programmer gives you DB10 "LineData" (non-optimized) with Speed : Real at offset 0.0 and Fault : Bool at 4.1.
- Add a Siemens S7 device at
192.168.0.10. - Manage Tags → Add Tag:
DB10/REAL/0, Data Type float, Display NameLine Speed. - Add Tag:
DB10/BOOL/4.1, Data Type bool, Display NameLine Fault.
Troubleshooting
| Symptom | Cause | Fix |
|---|---|---|
| Error — Could not reach device at IP:102 | IP wrong, port 102 blocked, or wrong rack/slot. | Ping the CPU; check Rack and Slot under Driver Settings. |
| Connected, reads Bad; log function refused by CPU | PUT/GET not permitted. | Enable PUT/GET and download. |
| Reads Bad; log Address out of range | DB doesn't exist, offset past the end, or optimized block access on. | Turn optimized access off; check offsets in the DB. |
| Values look wrong | Wrong offset or type (e.g. reading a REAL as INT). | Confirm offsets from the DB's Offset column. |
| Prefer symbolic names | The classic protocol has none. | Import symbols from TIA Portal (standard blocks), or use Siemens S7 (OPC UA) (any block). |
| A symbol tag reads Bad; log unknown S7 area | The symbol is no longer in the imported table. | Import the symbols again, or change the tag path. |
T/… or C/… reads Bad on an S7-1200/1500 | Those CPUs have no T and C areas. | Read the timer's or counter's instance DB instead. |